It's that time of the year again, the air has a chill and we are all busy getting ready for the holidays; and we have another great issue for you this month.

Thanks to all of the InfraMation delegates who completed our survey. We got great feedback and some ideas for next year.

Our bulletin boards have been busy this last month. Check out the latest posts.

Our application article this month tells how you can sometimes come to the incorrect conclusion from your thermal image if you don't do a little more digging. See "How The Eyes (and IR camera) Can Be Misled" by Joe Gierlach at TEGG Corporation.

And we have another Brainteaser for you at Brainteaser of the Month.

If you want to save this newsletter for viewing off line in your computer, just go to the web page using your browser and select File....Save As or save this email page as html in your email software.

Spend some quality time with your loved ones this holiday season. We'll see you again next year!

Gary Orlove,
Editor and Publisher

 

IR in the News [top]
  • THERMACAM® – The Alternative to Exhaustive Testing
    Process & Control Today, UK - Nov 26, 2003
    Thermal imaging has increasingly become a key tool at Land Rover for the early ... Without thermography there would only be evidence of total failure at the end of ...

  • The Truth Lies in Technology
    TechNewsWorld - Nov 10, 2003
    ... In Rochester, Minn., in 2001, endocrinologist James Levine was performing obesity research by using a thermal-imaging camera that observes how much heat is ...

  • Important Incan comples discovered near Machu Picchu
    The Arbiter Online - Nov 10, 2003
    ... A re-examination of Bingham’s expedition notes in the Yale archives, combined with thermal imaging studies conducted from a low-flying Cessna, allowed ...

  • What is RSD?
    Times Press, IL - Nov 7, 2003
    ... RSD is diagnosed primarily through observation of the symptoms. Some physicians use thermography to detect changes in body temperature that are common in RSD. ...

 

ITC Website Message Board Posts [top]

We recently overhauled the Infrared Training Center website. We have a new design, improved user interface, new features, and it runs much faster. Among the new features are a thermal image gallery and redesigned message boards.

Below you will find a selection of new topics started by visitors to the message board last month. Feel free to click the links, see how people have responded, and post your own response.

  • Heat Detection Underwater
    I am trying to determine if the heat of a human body or of a motor engine located underwater could be detected or visualized using infrared sensors or cameras, and whether the sensors or camera can be located several feet away from the heat source, e. g, 2 to 10 feet away. If the answer is yes, do the sensors/camera need to be underwater too? or airborne detection is also possible?

  • EIFS wall scans
    I tried to scan a wall system comprised of a rigid foam insulation and a synthetic stucco covering.  My scans were inconclusive.  Does anyone have specific experience to share?

  • CALIBRATION inquiry for Model: FLIR THERMACAM PM695
    What is the CALIBRATION procedure for Model: FLIR THERMACAM PM695 TYPE: THERMOSCANNER. Can anyone help us?

  • Reference temperature, background temperature
    The reference temperature setting in my ThermaCAM PM575 camera can be done manually. I am not sure what the reference temperature is referencing or if I am confusing it with background temperature. I am concerned about having inaccurate measurements.

And of course if YOU have a question or want to start a discussion on a topic, we would love to hear from you. Just post a new thread on the message board.

 

How The Eyes (and IR camera) Can Be Misled [top]

By Joe Gierlach
Manager - Technical Training & Support
TEGG Corporation

The IR camera is a great tool used in our everyday predictive maintenance endeavors, but it can play tricks on our eyes if we do not investigate beyond what we are observing. Things truly are not always as they seem, here's an example:

1) As indicated in the images below, we “appear” to have a hot spot and differential in temperature on the “C” phase of the breaker, just to the bottom of the actuator handle. (Remember to click all images for a larger view).

2) The operating parameters at the time of this visit were as follows: 

Rating 200 amps    
Loading “A” – 8 amps “B” – 48 amps “C” – 24 amps
THD%C “A” – <2% “B” – <2% “C” – <2%
Millivolt Drop “A” – .001 “B” – .001 “C” – .001

2)     

Relatively normal operating conditions in a generally climate controlled room, with no evidence of any reflective source of infrared radiation noted.

3) So why is there a temperature of nearly 40° C (104° F for those who relate to Fahrenheit)? With a high emissivity on the breaker itself, reflective effects would need to originate from a much higher heat source to have an effect on the observed actual temperature on the breaker.

4) How could the operating parameters be within guidelines, no apparent resistance increase was measured across the breaker contacts via milli-volt observation, harmonic distortion levels were deemed negligible, and the highest load demand on “B” phase DID NOT have the highest temperature rise?

The answer to this was revealed when the breaker manufacturer, Cutler-Hammer, assisted in the dilemma resolution. The source of the heat was determined to be an under voltage relay coil used in conjunction with the electronic sensing and trip unit, mounted under the case at the location illustrated above. The heat associated with electromagnetic induction properties or transformers and coils radiated to the breaker case and were detected by the IR camera.

The unit in question is illustrated in the blow up view, showing this can be either left or right hand mount.

Below is an assembled view illustrating physical location of where “heat” may be observed.

Another good example is illustrated below. A transformer with balanced loading well below its rating, low harmonic content, and no extreme conditions present in the surrounding environment “appears” to have a coil winding that has a temperature difference of nearly 10° C between “B” and “C” phase windings, as indicated by the arrow. The “B” phase winding was approximately 48° C and the “C” phase was approximately 41° C.

Based on those operating parameters, this is a problem as defined by NETA guidelines that is near the “Severe” range as related to our severity criteria levels. In fact, closer quantitative analysis of the thermogram reveals the reasons for the “apparent” differential temperature.

1) The “B” phase winding does not have the volumetric area to allow for natural convection cooling of the heat, thus it cannot dissipate heat as efficiently.

2) The core temperature is much higher as compared to the windings and the heat generated in this area will influence the winding temperatures if its effects are not compensated for. This causes a radiating of heat to impinge on the winding and affect the observed temperature.

3) The actual measured temperature does not exceed the manufacturer specified guidelines with respect to temperature.

Again this example illustrates the absolute need to provide quantitative analysis of any “apparent” thermal anomalies. Other surrounding factors had an effect on what we were observing and they had to be taken into consideration.

CONCLUSION

With the advent of solid-state protection in devices of this nature, this scenario is going to become more common. We cannot rely on what we see alone, and sometimes even the analytical tools at our disposal still fail to reveal the source of a problem.

The first example aids in demonstrating the absolute need to utilize milli-volt drop tests with respect to thermal anomalies, as it will provide one of several methods in assisting us to prove or disprove the presence of an actual problem, by effectively measuring and quantifying the passive resistance of a contact point using Ohms law, and allowing us to calculate I^2 R losses. With the lack of voltage drop and harmonic currents in this problem, we can safely determine the breaker contacts and terminations are suitable and heating is not related to non-linear loading.

To rely solely on temperature difference from similar components or ambient air is not enough for us to diagnose a problem such as this. Even the generalized guidelines in the NETA specs for electrical equipment cannot be relied upon as a rigid benchmark in this respect. If the NETA standards were applied in the above example, it would be approaching the  “Critical” level, as the temperature difference is compared to ambient is nearly 40° C. Is the case in the first example? Would you recommend an immediate outage to service this component? Not likely with the operating conditions noted. In the second example, the untrained eye would most certainly identify this as a problem based solely on differential temperature guidelines.

We must use all of our tools to draw accurate conclusions, as many factors need to be taken into consideration with respect to these types of situations. We cannot just assume that because a certain temperature differential exists, apparent or true, particularly with respect to direct measurement, that a problem exists. Making qualitative and quantitative analysis is key in keeping us one step above the rest. Sure a hot spot exists in these examples, but your eyes can deceive you if you do not give consideration to such variables as external influencing factors and load demands, and not provide proper compensation values to the camera for these factors.

Editor's note: Joe receives an InfraMation Executive Attaché for his article contribution.

 

Brainteaser of the Month  [top]

Here is this month's brainteaser. First reader to email me with the correct explanation of the thermogram receives a gift from ITC. Please put "Brainteaser" as the subject of the message.

Click here to email your guess

Do you have an interesting image that you think would stump other thermographers? If so please email me your image (preferably in native .img, .jpg, .tif, .tgw, or .tmw format) with an accompanying visible photo and explanation. If your image is used, you receive a gift as well.

 

Last Month's Brainteaser [top]

Click here for a larger imageOk, I guess a lot of thermographers are Trekkies because over 80% of the responses were correct!  Yes, this is a thermal image of a Ferengi. The ITC crew traveled "where no thermographer has gone before" to capture this rare image.

Our winner for last month's Brainteaser is Roland Karsch from Masonite Corporation. Roland receives our special low emissivity traveling coffee mug for his guess.

 

Past Issues  [top]

Click the links below to view past issues of this newsletter:

All past issues from February 2000 through December 2002

November 2003

October 2003

September 2003

August 2003

July 2003

June 2003

May 2003

April 2003

March 2003

February 2003

January 2003

 

Upcoming Classes  [top]

Click the links below to see our latest course calendars (in local language).

Americas - Level I

Americas - Level II

Americas - Application, Level III, R&D

Eurasia

Deutschland

France

Italia

United Kingdom

 

About the Infrared Training Center  [top]

The Infrared Training Center offers training and certification in all aspects of infrared thermography use. Our world-class training facilities are located near Boston, Massachusetts, USA and Stockholm, Sweden and have the world's most extensive hands on laboratories for infrared applications. Please join us in exploring the fascinating world of the infrared!

Your comments and suggestions about this newsletter are welcomed and encouraged. If you have an interesting application or case study to share, we encourage you to submit it for publication. Published articles earn credit towards recertification.

Please e-mail Gary Orlove or send regular mail to the Americas office.

Visit our website:

ITC Americas, BOSTON

16 Esquire Road
N. Billerica, MA 01862, USA

Tel: +1-978-901-8405
Toll free: +1-866-TRAINIR
                 (866-872-4647)
Fax: +1.978.901-8832
E-mail:
mailto:info_us@infraredtraining.com

ITC Eurasia, SWEDEN

Rinkebyvägen 19
SE-182 11 Danderyd, Sweden

Tel: +46 (0) 8 753 25 00
Fax: +46 (0) 8 753 26 01
E-mail:
mailto:itc@flir.se

THIS DOCUMENT IS FOR INFORMATIONAL PURPOSES ONLY. INFORMATION PROVIDED IN THIS DOCUMENT IS PROVIDED 'AS IS' WITHOUT WARRANTY OF ANY KIND. The user assumes the entire risk as to the accuracy and the use of this document. The Infrared Training Center newsletter may be copied and distributed subject to the following conditions: 1. All text and images must be copied without modification and all pages must be included; 2. All copies must contain the Infrared Training Center copyright notice and any other notices provided therein;
3. This document may not be distributed for profit