Infrared Helps Solve the Case of the Thirsty Fountain

When the final phase of a several-acre shopping mall complex outside of Birmingham, AL was completed about five years ago, the developer installed a 400,000 gallon fountain to set off the beautiful surrounding scenery provided by its landscape. Since then, they started paying around ten thousand dollars a month more than their expected water bill for this addition, which they assumed was a result of evaporation from the fountain spray, since the fountain water itself is recirculated.

But when the fountain went down for repairs about a year ago, the water bill stayed almost the same. So they called in a leak detection service, which ran statistics research on the meters and flow valves only to come to the conclusion that the mall was losing the water around the clock, and not just during fountain operation hours. These tests cost the mall thousands of dollars, but provided no conclusive evidence as to where the loss was occurring.


Infrared Helps Solve the Case of the Thirsty Fountain

Birmingham-based LeakTite Consultants, Inc. (dparker@Icicorp.net) was then asked to investigate the massive water loss. Using its FLIR ThermaCAM® B-1 infrared camera in a little over 5 hours, they were able to detect temperatures variances in the sod overlay, and confirm that the wet areas were coming from either ground water, or from city-supplied sources, Using a simple, hardware store pool chemical testing kit, LeakTite was then able to identify the areas with high chlorine content and thus isolate the water coming from the city. They immediately dug in those areas and found that a 1-inch reserve supply line to the fountain had never been connected during construction, and water had been flowing freely for the past five years.

The end of the reserve supply line was connected it to the fountain with six feet of sch-40 pvc pipe and 2 compression couplings, then the area was back-filled and the landscaping restored. Total repair cost was less than $1000.

The use of the B-1 to identify the problem saved the cost of having to dig up all of the supply lines – at a savings of over $100,000 in excavating, re-paving and re-landscaping costs. And, of course, the elimination of the problem is now saving the mall over $120,000 per year on their water bill.

How did you like this article?
IR Solves Case of the Thirsty Fountain
Fantastic - I will recommend it to others
Very good - I learned a lot
OK
Not so hot - I didn't get much out of it
Bad - this did nothing for me

view results
 

 

About the Infrared Training Center 

The Infrared Training Center offers training and certification in all aspects of infrared thermography use. Our world-class training headquarters are located near Boston, Massachusetts, USA and Stockholm, Sweden and have the world's most extensive hands on laboratories for infrared applications. In addition, we have training centers around the world. Please join us in exploring the fascinating world of the infrared!

Your comments and suggestions about this newsletter are welcomed and encouraged. If you have an interesting application or case study to share, we encourage you to submit it for publication. Published articles earn credit towards IR recertification.

Please e-mail Gary Orlove or send regular mail to the Americas office.

Visit our website:


ITC Americas, BOSTON

16 Esquire Road
N. Billerica, MA 01862, USA

Tel: +1-978-901-8405
Toll free: +1-866-TRAINIR
                 (866-872-4647)
Fax: +1.978.901-8832
E-mail:
mailto:info_us@infraredtraining.com


ITC Eurasia, SWEDEN

Rinkebyvägen 19
SE-182 11 Danderyd, Sweden

Tel: +46 (0) 8 753 25 00
Fax: +46 (0) 8 753 26 01
E-mail:
mailto:itc@flir.se

 

THIS DOCUMENT IS FOR INFORMATIONAL PURPOSES ONLY. INFORMATION PROVIDED IN THIS DOCUMENT IS PROVIDED 'AS IS' WITHOUT WARRANTY OF ANY KIND. The user assumes the entire risk as to the accuracy and the use of this document. The Infrared Training Center newsletter may be copied and distributed subject to the following conditions: 1. All text and images must be copied without modification and all pages must be included; 2. All copies must contain the Infrared Training Center copyright notice and any other notices provided therein;
3. This document may not be distributed for profit

©2005 Infrared Training Center  - All rights reserved